Power Factor Correction Application Guide | Location | Capacitor At Load

Power Factor Correction Application Guide

LOCATION OF REQUIRED CAPACITORS

METHOD #1: CAPACITOR AT LOAD
Install a single capacitor at each sizeable motor and energize it whenever the motor is in operation. We refer to this as Calmount® brand capacitor (Capacitor At Load). Tables 2 and 3 show suggested kVAR ratings to be selected.

This method usually offers the greatest advantages of all, and the capacitors could be connected either in location (A) or (B) in Figure 4 below:



Location A - Normally used for most motor applications.

Location B - Used when motors are jogged, plugged, reversed; for multi-speed motors, or reduced-voltage start motors.

The advantages of method #1 are many:

  1. Corrects Power Factor, unloads the transformer, reduces losses in conductors (KW-Hrs) from source to motor location.
  2. Voltage drop to motor is reduced - thus optimizing motor performance.
  3. Installation simple - no new switches or circuit breakers required.