Typical Applications
Case 1
Recommendation: Select a 3% Line Reactor sized per the voltage and horsepower from the Myron Zucker, Inc. catalog. Connect on the input as follows: Case 2
Recommendation: Select a 5% Line Reactor sized per the voltage and horsepower from the Myron Zucker, Inc. catalog. Connect on the output as follows: Case 3 For harmonic reduction on motor drive circuits with no power factor correction capacitors on the secondary side of the industrial plant transformer and no power factor penalty imposed by the utility company, use the following: Recommendation: Select a 5% Line Reactor sized per the voltage and horsepower from the Myron Zucker, Inc. catalog. Connect on the input as follows: Case 4 In facilities which have power factor penalties and power factor correction capacitors are installed, or there are plans to install power factor correction capacitors, the following should be used: If existing power factor correction capacitors are installed and Adjustable Speed Drives (ASDs) are being added, then harmonic filters must be installed on each ASD or group of ASDs. Contact Myron Zucker, Inc. regarding Traps/filters and their applications. To isolate the in-plant power factor correction capacitors, a Line Reactor must be installed on the line side of the harmonic Trap/filter. Recommendation: Select a 5% Line Reactor sized per the voltage and horsepower from the Myron Zucker, Inc. catalog. Connect on the input as follows: |
|