AUTOCAPACITRAP™ Brand Harmonic Filters - Main Service Entrance
AUTOCAPACITRAP Brand Harmonic Filter Series

 
 
ENCLOSURE DIMENSIONS
ENC. H W D
F2 74.00 31.00 30.00
F3 84.00 46.00 30.00
All dimensions are in inches. Myron Zucker, Inc. reserves the right to change dimensions without notice.
STANDARD SELECTION CHART
240V / 3Φ / 60Hz
 
480V / 3Φ / 60Hz
 
600V / 3Φ / 60Hz
kVAR
PART NUMBER
STEP SIZE
AMPS*
ENC.
 
kVAR
PART NUMBER
STEP SIZE
AMPS*
ENC.
 
kVAR
PART NUMBER
STEP SIZE
AMPS*
ENC.
                                 
75
ACIM33075-3H5
25
198
F2
 
150
ACIM53150-3H5
50
198
F2
 
150
ACIM73150-3H5
50
159
F2
100
ACIM33100-3H5
25
265
F2
 
200
ACIM53200-3H5
50
265
F2
 
200
ACIM73200-3H5
50
212
F2
125
ACIM33125-3H5
25
331
F2
 
250
ACIM53250-3H5
50
331
F2
 
250
ACIM73250-3H5
50
265
F2
150
ACIM33150-3H5
25
397
F2
 
300
ACIM53300-3H5
50
397
F2
 
300
ACIM73300-3H5
50
318
F2
175
ACIM33175-3H5
25
463
F3
 
350
ACIM53350-3H5
50
463
F3
 
350
ACIM73350-3H5
50
370
F3
200
ACIM33200-3H5
25
529
F3
 
400
ACIM53400-3H5
50
529
F3
 
400
ACIM73400-3H5
50
423
F3
250
ACIM33250-3H5
25
662
F3
 
500
ACIM53500-3H5
50
662
F3
 
500
ACIM73500-3H5
50
529
F3
300
ACIM33300-3H5
50
794
F3
 
600
ACIM53600-3H5
100
794
F3
 
600
ACIM73600-3H5
100
635
F3
 
* The ampacity of capacitor circuit conductors shall not be less than 135% of the rated circuit of the capacitor per NEC 2008
NOTE: The above part numbers are for the 5th harmonic. For other harmonic applications, change the part number suffix.
EXAMPLE: 7th = H7, 11th = H11, etc.